Settings

BT30
AA1-X3
AA1-SF2
AA1-X7
ELECTRICAL ADDITION - MAXIMUM OUTPUT
The immersion heater output is divided into steps, ac-
cording to the table.
Setting maximum output in the electric additional heat
is done in menu 5.1.12.
Power steps of the immersion heater
Electrical addition (kW)
0.0
2.7
1
5.3
8.0
1
Factory setting
The table displays the maximum phase current for the
relevant power step for the heat pump.
EMERGENCY MODE
When the heat pump is set to emergency mode (SF1
is set to
), only the most necessary functions are ac-
tivated.
• The compressor and fans are off and heating is man-
aged by the immersion heater.
Power in emergency mode
The immersion heater's output in emergency mode is
set with the dipswitch (S2) on the immersion heater
circuit board (AA1) according to the table below.
kW
1
2
2.7
on
off
1
5.3
on
off
8.0
on
off
1
Factory setting
28
Chapter 5 | Electrical connections
Max (A)
6.3
17.9
29.3
41
3
4
5
6
off
off
off
off
on
off
off
off
on
off
on
off
The image shows the dip-switch (AA1-S2) in the factory
setting.