4.4 BACnet Objects and Network Configuration
Transmission type
•
Physical layer: Wi-Fi 802.11 b/g/n
•
Protocol: BACnet/IP
•
UDP Port Number: BAC0 (47808)
•
MAC address: Wi-Fi chip MAC address found written on the back side of thermostat or in
Engineering Menu item (Phy3). This can assist when multiple Wi-Fi thermostats are
installed.
•
Device Instance: 700001
Initial Configuration
All configuration parameters are settable through use of the buttons on thermostat by entering
the Engineer Menu, or once installed on the BACnet network, configuration can also be altered
using BACnet commands. Network command-based configuration can also be accomplished on
the bench using a Wi-Fi enabled laptop/computer/tablet/smart phone and Contemporary
Controls' free
BACnet Discovery Tool.
Wi-Fi Communication Configuration
Overview
The BASstat Wi-Fi thermostat is preconfigured with a BACnet Device Instance of 700001 and a
UDP Port Number of 47808 (decimal) equivalent to BAC0 (hexadecimal). To alter this
configuration, enter the Engineering Menu by holding down the UP and DOWN buttons
simultaneously for 5 seconds. Use the UP and DOWN buttons to navigate through the menu and
change menu item values. Use the MODE button to enter a menu item and accept/confirm a
selected value. To exit the Engineering Menu, navigate to menu item (End) and press MODE, or
the menu will exit automatically when not used after 5 seconds.