6. Insert the batteries into the sensor. Wait approximately 20 seconds for the control panel screen to display:
"I.S. [x] Added as Sensor [y]." The LED on the sensor will turn solid for 5 seconds once the sensor has
enrolled.
7. Perform another panel comm-test to ensure that Alarm.com receives the updated device equipment list.
This will speed up the sensor initialization process.
The zone will be configured as a virtual zone and programmed automatically into the next available slot in
l
section [560][001]-[032] starting at zone 126 and counting down for each additional Image Sensor added.
Once enrolled, the Image Sensor will appear as a normal zone.
l
By default, the Image Sensor is enrolled as an Interior Stay/Away zone in zone type 005. Zone type and
l
attributes can be assigned in the installer menu, in a similar way as regular zones. For more information,
refer to the "Zone Setup" section of the PowerSeries Neo Alarm Controller Reference Manual.

Panel Settings

Night Arming

The panel has the ability to night arm, which arms the perimeter and restricts movement to designated interior
areas. Night arming via the panel should be restricted to one of the five function keys. For more information on
Night Arming and how to program the function keys, see the installation guide provided with the panel.

Central Station and Telephone Line Settings

Central Station and telephone line settings will be automatically configured through the CS Forwarding Set-
tings page of the Alarm.com Dealer Site. The following are the panel settings that will be configured via the
Dealer Site page (when required) and should not be configured in the panel:
Section
Option
015
7
300 [001]
--
300 [002]
--
300 [003]
--
300 [004]
--
301 [001]
--
301 [002]
--
301 [003]
--
301 [004]
--
309 [001]
--
309 [002]
--
310 [000]
--
310 [001]
--
310 [002]
--
310 [003]
--
310 [004]
--
310 [005]
--
310 [006]
--
310 [007]
--
310 [008]
--
311 [001]
--
Description
Telephone line monitoring
Panel Communication Path - Receiver 1
Panel Communication Path - Receiver 2
Panel Communication Path - Receiver 3
Panel Communication Path - Receiver 4
Communication telephone number 1
Communication telephone number 2
Communication telephone number 3
Communication telephone number 4
System Call Direction - Maintenance
System Call Direction - Test Transmission
System account number
Partition 1 account number
Partition 2 account number
Partition 3 account number
Partition 4 account number
Partition 5 account number
Partition 6 account number
Partition 7 account number
Partition 8 account number
Partition 1 Call Direction - Alarm/Restore
- 13 -