5

Product information

5.1

Type key

5.2

Technical data

Property
Rated speed
Nominal diameters DN
Permissible min./max. fluid temperature
Max. ambient temperature
Maximum permissible operating pressure 10 bar
Insulation class
Protection class
Pipe and pressure measurement connec-
tions
Approved fluids
Electrical connection
Motor protection
Speed control
Explosion protection
Suitability for potable water
28
The type key consists of the following elements:
Example:
IPL/DPL 50/115-0.75/2 (N) (P2)
IPL
Flange-end pump as Inline pump
DPL
Flange-end pump as Double pump
50
Nominal diameter DN of the pipe connection [mm]
115
Nominal impeller diameter [mm]
0.75
Nominal motor power P
2
Number of motor poles
N
With standard motor/plug shaft
P2
Standard version variant: Potable water approval acc.
to ACS (see www.wilo.com)
K1
Standard version variant: Outdoor installation
"Western European climate" (motor with protective
fan cover)
K4
Standard version variant: Outdoor installation
"Western European climate" (motor with protective
fan cover, additional standby heating 1~230 V)
K3
Standard version variant:
3 PTC thermistor sensors
Value
2900 or 1450 rpm
IPL: 25 to 100
DPL: 32 to 100
-20 °C to +120 °C
(depending on the fluid and type of mechanical
seal)
+ 40 °C
F
IP 55
PN 16 flange in accordance with EN 1092-2
With pressure measuring connections Rp
In accordance with DIN 3858
Heating water according to VDI 2035
Cooling/cold water
Water/glycol mixture up to 40 Vol.-%
3~400 V, 50 Hz,
3~230 V, 50 Hz,
(up to 3 kW inclusive)
Required onsite
Control devices
(Wilo-VR system, Wilo-CC system)
As a special version, only possible for model ...-N
in conjunction with the Wilo supplementary ATEX
installation and operating instructions for pump
types:
Wilo-Crono... IL/DL/BL,
Wilo-Vero... IPL-N/DPL-N, IPS, IPH-W/O
Possible as special version P2.
Observe Wilo supplementary installation and
operating instructions "Wilo-IPL & IP-E
variant P2".
[kW]
2
Remarks
1
/
8
For special versions,
e.g. for other voltages,
operating pressures,
fluids, etc. see rating
plate or visit
www.wilo.com.
WILO SE 11/2017