 Connection diagram
• A connection diagram of the emergency drive (commercial mode) is as follows.
Emergency drive execution
*1
Be careful of the capacity of the sequence output terminals.
The applied terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
Output terminal capacity
Open collector output of inverter
(RUN, SU, IPF, OL, FU)
Inverter relay output
(A1-C1, B1-C1, A2-B2, B2-C2)
Relay output option
(FR-A8AR)
*2
When connecting a DC power supply, insert a protective diode.
When connecting an AC power supply, use relay output terminals of the inverter or contact output terminals of the relay output option
(FR-A8AR).
*3
The applied terminals differ by the settings of Pr.180 to Pr.189 (Input terminal function selection)
*4
The applied terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
NOTE
• Be sure to provide a mechanical interlock for MC2 and MC3.
MCCB
R/L1
S/L2
T/L3

X84
Inverter/bypass
CS
Reset
RES
SD
Output terminal permissible load
24 VDC 0.1 A
230 VAC 0.3 A
30 VDC 0.3 A
MC2
MC3
U
V
W

Y65
Emergency drive in operation

Fault output during emergency drive
ALM3
MC2
MC3

MC2
MC3
MC2

MC3
SE
2
IM

24VDC
BCN-C22005-957