Installation

4.1
Select suitable installation location
Assembling the system:
Select a room with good aeration and/or ventilation as
well as a level assembly surface with adequate load-bear-
ing capacity.
Ensure room temperature with frost protection and a max-
imum temperature of 45°C (max. 80% humidity).
Room height at least 60 cm higher than the system so
that the auger screw can be tilted during maintenance
work.
1
This reduces the risk of the siphon and odour traps becoming sucked dry. Less air input and movement as well as less
odour and foaming in the system.
60 / 92
Ensure clear working space, at least 1m all around the
system.
Inlet with stilling section with length at least 10 x "DN of
the inlet pipe" (2% gradient). Equip the transition from
the building downpipe to the stilling section with 2 x 45°
bends.
4.2
WARNING
Transport risk / system's own weight!
WARNUNG
Use suitable lifting gear (e.g. cable winch or forklift)
to erect lying components. Use lifting eyes attached
to coarse filter unit for safety.
Installation and operating instructions
1
Safe assembly
Check the weight of the system / system compo-
nents (see "Technical data", page 56).
Pay attention to correct lifting and ergonomic fac-
tors.
Lift the system with a crane only, if a lifting eye
has been attached to it in the factory (customised
solution).
016-141_01