3.4.7 AC Wiring of M100A_284

- Always no energy on the AC power cables during the cable installation to
prevent electrical hazard.
M100A_284
N
L2
AC entry - 28.9 mm
trade size gland
Figure 3-16: Location for AC terminal of M100A_284
(1) Ensure the AC disconnect device is in "OFF"
(2) Strip off the insulation of each cable by 30mm.
(3) For the aluminum conductor, remove the oxide film of the conductor surface
and apply the protective grease.
(4) Pass the cable of L1, L2, L3 or neutral (if required) through each M40 cable
gland with the proper inner rubber.
(5) Follow the label to Connect L1, L2, L3 and neutral (if required).
(6) Tighten all screws of the terminal with 42.4 N-m torque.
(7) Fasten all AC cable glands for sealing.
DANGER : ELECTRICAL HAZARD!!
L3
L1
After inserting conductor, torque
terminal nut by 42.4 N • m
35
Installation
N
L3
L2
L1