VAT 64246-UEHC-0001 Installation, Operating, & Maintenance Instructions page 37

Control gate valve with logic interface
Table of Contents

Advertisement

Series 642
4.6.6.1
Gain factor adjustment
The gain factor effects: Stability, Response time
Default value is 1. Adjustment range is from 0.0001 to 7.5.
Higher gain results in:
Lower gain results in:
Adjustment procedure:
1. Start with gain factor 1.0
2. Open valve.
3. Control a typical pressure / flow situation.
4. Repeat from step 2 with lower (higher) gain factors until optimal pressure response is achieved and
stability is ok.
Local operation:
('Control View', 'Control Performance Analyzer'
or 'Service Box 2')
Set gain factor in menu 'Setup / Control
Parameter'
603685EA
INSTALLATION
faster response
slower response
Normally adjustments down to gain factors of 0.42 should lead to good results.
Otherwise you may need to improve sensor connection. Refer to «Requirements to
sensor connection».
Edition 2013-08-22
higher over- / undershoot of pressure
lower over- / undershoot of pressure
Remote operation:
It's not possible to do 'Gain factor adjustment' via
remote operation.
37/73