DIGITAL INDICATOR
USER'S MANUAL
RI-10W (VER 214A)
RI-20W (VER 214A)
RI-25W (VER 214A)
RI-27W (VER 214A)
RI-30W (VER 214A)
RI-50W (VER 214A)
RI-148A,B (VER 214A)
Ver 214A

Advertisement

Table of Contents
loading

Summary of Contents for Radian RI-10W

  • Page 1 Ver 214A DIGITAL INDICATOR USER’S MANUAL RI-10W (VER 214A) RI-20W (VER 214A) RI-25W (VER 214A) RI-27W (VER 214A) RI-30W (VER 214A) RI-50W (VER 214A) RI-148A,B (VER 214A) Address : #1604, 53, Gasan digital 2-ro, Geumcheon-gu, Seoul, Republic of Korea http://www.radian21.com E-Mail : info@radianqbio.com...
  • Page 2: Table Of Contents

    8-1. Types of Setting mode & Set-up  18 8-2. Function mode (Function Set-up)  19 1) RI-10W, RI-20W, RI-25W, RI-27W, RI-50W, RI-148A,B function set-up  19 2) RI-30W function set-up  20 3) How to change the REALY setting  21 8-3.
  • Page 3: Features

    RADIANQBIO INSTRUMENT www.radian21.com 1. Features We thank you for using our product. Please refer to this manual or contact our office if you find any problems during using our product. This product is an indicator that emplifies the micro voltage signals from each sensor and display in digital.
  • Page 4: Attention

    RADIANQBIO INSTRUMENT www.radian21.com 2. Attention For the efficient and safe use, please carefully read and be fully aware of the following details before using this product. It is strictly forbidden to use this product for any other purpose of use or to attempt to make any alteration on this product.
  • Page 5: Specification

    RADIANQBIO INSTRUMENT www.radian21.com 3. Specification Spec. Model RI-10W RI-50W RI-30W RI-148A Strain Gauge PROXIMITY Available sensor Strain Gauge sensor sensor SENSOR SIGNAL 0.5 ~ 3mV/V pulse 0.5 ~ 3mV/V EXCITATION DC 5V 70mA DC 5V 70mA -19999 ~ Upper limit Display...
  • Page 6 RADIANQBIO INSTRUMENT www.radian21.com Spec. Model RI-20W RI-25W RI-27W RI-148B Differential Voltage, current HBT(Half type) Available sensor torque Potentiometer sensor trans (Option : LVDT) Potentiometer sensor DC0~10V or 4~20mA SIGNAL AC0~2Vrms 0.5~2mV/V DC0~10V (Option : ±10V) DC10V or 24V 60mA EXCITATION (Option : ±15V AC2Vrms 5kHz DC5V 70mA...
  • Page 7: Front Panel

    RADIANQBIO INSTRUMENT www.radian21.com 4. Front panel ⑴ RI-10W, RI-20W, RI-25W, RI-27W, RI-30W, RI-50W ① comparison output Indication LED: The LED lights up when the Relay is in contact output state. ② HOLD Indication LED: This LED will be lighted when the measured value is on Hold.
  • Page 8 RADIANQBIO INSTRUMENT www.radian21.com ⑵ RI-148A, RI-148B ① HI, LO Indication LED: LED will be lighted when measured value exceeds the setting value. ⑧ HOLD Indication LED: This LED will be lighted when the measured value is on Hold. ⑨ MOD : Measured value stable (on), unstable (off) indication ④...
  • Page 9: Rear Panel

    5. Rear panel ⑴ RI-10W, RI-20W, RI-25W, RI-27W, RI-30W, RI-50W Please check the location of terminal and its use. While the projected button is being pressed, please insert the cable into the lower hole completely. As soon as you release the button, the connection will be completed.
  • Page 10 ○ : RELAY3( Normal) Output Terminal (OK ) ○ : RELAY 4 Output Terminal ○ SW1, 2 • RI-10W, RI-25W, RI-27W, RI-30W, RI-50W : NC • RI-20W : Sensor supply voltage setting Sensor output signal setting DC10V DC24V 0 ~ 10V 4 ~ 20mA ※...
  • Page 11 RADIANQBIO INSTRUMENT www.radian21.com ④ SIG+ : Sensor Ouput Signal + Connection Terminal ⑤ SIG- : Sensor Output Signal – Connection Terminal ⑥ GND : SHIELD connection terminal of sensor ⑦ : Ground Terminal (as an independent ground connection.) ⑧ INC : External Input Common Terminal ⑨...
  • Page 12: Wiring Diagram

    RADIANQBIO INSTRUMENT www.radian21.com 6. Wiring Diagram ⑴ RI-10W, RI-50W ⑵ RI-20W...
  • Page 13 RADIANQBIO INSTRUMENT www.radian21.com ⑶ RI-25W ⑷ RI-27W ⑸ RI-30W...
  • Page 14 RADIANQBIO INSTRUMENT www.radian21.com ⑹ RI-148A, RI-148B ⑺ Example - External Input PLC Connection...
  • Page 15: Components & Function

    RADIANQBIO INSTRUMENT www.radian21.com 7. Components & Function 7-1. How to use Hold mode Hold mode is largely divided into Peak Hold and Sample Hold. Please select Peak or Sample. To input Hold, you can use Hold key on the front panel or external input. For the operation method, please refer to the drawing below.
  • Page 16: How To Use Comparison Output Function

    RADIANQBIO INSTRUMENT www.radian21.com 7-2. How to use comparison ouput function For comparison output function, there are 4 different modes such as Decision, High limit, Low limit, Low&High limit. It displays through the relay of rear panel comparing each setup value. On limit mode, Hysteresis can be used.
  • Page 17 RADIANQBIO INSTRUMENT www.radian21.com...
  • Page 18 RADIANQBIO INSTRUMENT www.radian21.com * Note) In Function mode, if the value of F-13 is set the Base Offset (page26), the comparative output operates as follows. 1) Decision mode : Measured Value ≤ (Offset-Lower limit setup value) ⇒ RY1 ON (Low) Measured Value ≥...
  • Page 19: Setting Mode

    RADIANQBIO INSTRUMENT www.radian21.com 8. Setting Modes 8-1. Types of Setting mode & Set-up For setting mode, there are 3 different types of mode such as Function mode, Digital calibration mode and Actual load calibration mode. Mesuring mode While key is being Press, press Function mode ①...
  • Page 20: Function Mode (Function Set-Up)

    RADIANQBIO INSTRUMENT www.radian21.com 8-2. Function mode 1) How to set function (for RI-10W, RI-20W, RI-25W, RI-27W, RI-50W, RI-148A,B) The setting value of Function mode (page 22~29) can be changed the key operation below. (F-00~F-52) Measuring mode While key is being...
  • Page 21: Ri-30W Function Set-Up

    RADIANQBIO INSTRUMENT www.radian21.com 2) How to set function (for RI-30W) The setting value of Function mode (page 22~29) can be changed the key operation below. (F-00~F-52) Measuring mode While key is being Press, press Change to Select and save by key.
  • Page 22: How To Change The Realy Setting

    RADIANQBIO INSTRUMENT www.radian21.com 4) How to set RELAY data ① Decision mode (F-20 Decision mode: mode: 0) In the measuring mode, press the front key(RY1) or key(RY3) to display the currently set value, change it to the desired value, and press the key to save it.
  • Page 23: Function List

    RADIANQBIO INSTRUMENT www.radian21.com 8-3. Function list Name Function Setting Standard setup value Decimal point 0, 1, 2, 3 F-00 Pulse/circle (RI-30W) 0 ~ 360 F-01 Division 1, 2, 5, 10, 20, 50 F-02 Display filter 0.01, 0.02, 0.05, 0.10, 0.20, 0.50, 1.00 0.20 F-03 Hold mode Sample, Peak, Absolute, A/D...
  • Page 24 RADIANQBIO INSTRUMENT www.radian21.com ※ X : No Function RI-10W RI-20W Name Function RI-30W RI-148 RI-50W RI-25W,27W Decimal point ○ ○ ○ F-00 Pulse/circle (RI-30W) ○ F-01 Division ○ ○ ○ ○ F-02 Display filter ○ ○ ○ ○ F-03 Hold mode ○...
  • Page 25 RADIANQBIO INSTRUMENT www.radian21.com F-00. Decimal point (Decimal point Set-up) ① Decimal point : RI-10W, RI-20W, RI-25W, RI-27W, RI-50W, RI-148A,B (Standard setup value : 1) Display data 00000 : No decimal point 0000.0 : One decimal place 000.00 : Two decimal places 00.000 : Three decimal places...
  • Page 26 Note) When set to A/D Peak Hold (+), the Hold operation is performed according to the A/D input (output of the sensor), regardless of the sign of the F-50 Display reverse mode. RI-10W, RI-20W, RI-25W, RI-27W, RI-148A,B : 200Hz RI-50W : 1kHz F-04.
  • Page 27 RADIANQBIO INSTRUMENT www.radian21.com F-12. Auto zero during operation (Setting Zero when operationg) (Standard setup value : 0) Display data Setting Not used Autozero only once after power-on F-13. Base offset (Setting value) Base (Standard setup value : 00000) Display data Setting -19999 00000...
  • Page 28 RADIANQBIO INSTRUMENT www.radian21.com F-30. DAC mode (Setting Analog output type) ① RI-10W, RI-25W, RI-27W, RI-50W, RI-148A,B (Standard setup value : b_10V) Display data Setting b_05v -5 ~ +5V output bidirectional, polarity b_10v -10 ~ +10V output b_02A 0 ~ 20mA output...
  • Page 29 NOTE 2) When set to high speed DAC, the analog output is flexible according to the A/D input value (output of the sensor) and is not affected by the Hold action, F-13 Base offset, or the F- 50 Display reverse mode setting. NOTE) RI-10W, RI-20W, RI-25W, RI-27W, RI-148A,B : 200Hz RI-50W : 1kHz F-33.
  • Page 30 RADIANQBIO INSTRUMENT www.radian21.com F-41. Baud rate (Communication Speed Setup) (Standard setup value : 9.60) Display data Setting 2.40 2400 bps 4.80 4800 bps 9.60 9600 bps 19.20 19200 bps 38.40 38400 bps 57.60 57600 bps PRINT PRINT DATA OUT (PT-100) F-42.
  • Page 31 RADIANQBIO INSTRUMENT www.radian21.com F-51. Force unit (Conversion unit set up) (Standard setup value : 0) Display data Setting kg/㎠ kgf × 9.8 ℓb kgf × 2.2 kg/㎠ × 0.98 kg/㎠ × 0.098 Note1) When setting the conversion unit (set value: 1 to 4), calibration modes of 8-3 and 8-4 are not available.
  • Page 32: Digital Calibration (Calibration By Sensor Output Value)

    8-4. Digital calibration (Calibration by sensor output value) 1) RI-10W, RI-27W, RI-50W, RI-148A,B At the time of purchasing sensor, the rated capacity (R.C) and rated output (R.O) declared on the calibration sheet can be used for the calibration for easier calibration.
  • Page 33 RADIANQBIO INSTRUMENT www.radian21.com 2) RI-20W At the time of purchasing sensor, the rated capacity (displacement) and rated output (R.O) declared on the calibration sheet can be used for the calibration for easier calibration. Refer to 8-5.Actual load calibration if you need to correct the error. Measuring mode While key is being Press, press...
  • Page 34 RADIANQBIO INSTRUMENT www.radian21.com 3) RI-25W At the time of purchasing sensor, the rated capacity (displacement) and rated output (R.O) declared on the calibration sheet can be used for the calibration for easier calibration. DP-xx series (Half type (HBT) recommends setting the rated output value to approximately 0.3300.
  • Page 35 RADIANQBIO INSTRUMENT www.radian21.com 8-5. Actual load calibration (Exact Load Calibration) 1) Compensation Calibration (a) Please calibrate by 8-4 Digital Calibration. And, if there is a difference from the actual load value, you can change the indicator's display value to the actual load value by referring to the actual load calibration setup flow chart below.
  • Page 36 RADIANQBIO INSTRUMENT www.radian21.com 2) Compensation functions and notice If the actual load (load, displacement, pressure) is applied to the sensor and there is a difference between the value displayed in the indicator and the actual load value, the display value of the indicator can be changed to the actual load value. Up to 9 points can be stored. As the calibration interval is differentiated, the linearity of the sensor can be increased.
  • Page 37 3) If the output of sensor is unknown ① Notes for calibrating RI-10W, RI-27W, RI-50W, RI-148 Calibrate with 8-4 Digital Calibration. Deletes the data of the actual load calibration value. Then enter the output and capacity values as default (3.0000/30000).
  • Page 38 RADIANQBIO INSTRUMENT www.radian21.com ② Notes for calibrating RI-25W Set calibration with 8-4 Digital Calibration to delete the data of the values changed by the actual load calibration. At this point, the rated output value is 0.6%, and the rated capacity (displacement) of the sensor is set for the sensor.
  • Page 39: Da T A Ba Ck - U P & R Es T Or

    RADIANQBIO INSTRUMENT www.radian21.com 8-5. DATA BACK-UP & RESTORE You can save all the set-up values of the device and then restore them to the current set-up state as per your need. ◦ DATA BACK-UP : Save the current set-up state. ◦...
  • Page 40: Lock Set-Up

    RADIANQBIO INSTRUMENT www.radian21.com 8-6. Lock Set-up You can prevent any accidental operation due to the unnecessary key control by Lock set-up. After finishing calibration, it is recommended to set the Lock. At the first stage, please start while the power is OFF. Related Function when Lock is set : Function related to calibration.
  • Page 41: Product Inspection

    RADIANQBIO INSTRUMENT www.radian21.com 9. Product Inspection Symptom Cause Action  Load cell is damaged.  Load cell input, output. When Display  Load cell insulation resistance.  Check resistance trembles.  Indirect occurrence  Check load cell’s insulation resistance.  Loadcell faulty ...
  • Page 42 RADIANQBIO INSTRUMENT www.radian21.com When the measured • Faulty cable connection • Prove proximity sensors operation (Lamp) value does not • Faulty detection of • Check the distance between the proximity increase or proximity sensors sensor and the gear (approximately 1mm) increases slightly •...
  • Page 43: Bcd Output Interface

    RADIANQBIO INSTRUMENT www.radian21.com 10. OPTION 10-1. BCD OUT INTERFACE This Programmable BCD interface is the output for the weight value made into BCD coding. This interface is available for PLC(Programmable Logic Control), Computer.  PIN Arrangement PIN No. SIGNAL PIN No. SIGNAL Negative Polarity 1 ...
  • Page 44 RADIANQBIO INSTRUMENT www.radian21.com  Signal output DATA output TIME(T) can set to Function F-04 BCD Mode. (50, 100, 200, 500, 1000㎳)  Signal logic ① BCD DATA output : Negative logic (Negative) ② BUSY output : DATA READ = L ③...
  • Page 45: Serial Communication

    RADIANQBIO INSTRUMENT www.radian21.com 10-2. Serial communication Since RS232C Interface is very sensitive of electric noise. So please do the wiring from AC Power and electric wires separately. Also you must use the shield calbe always. 1) Wiring ① Option-02 (RS232C) Indicator Host PC TXD(Transmission Data)
  • Page 46: Protocol

    RADIANQBIO INSTRUMENT www.radian21.com 10-3. Protocol Standard protocol ① Stream mode (F-40, ID Number setup value ‘000’) (Ex. Data +1234.5 transmission) CODE BYTE1 BYTE2 BYTE3 BYTE4 BYTE5 BYTE6 BYTE7 BYTE8 ASCII CODE BYTE9 BYTE10 BYTE11 BYTE12 BYTE13 BYTE14 BYTE15 BYTE16 ASCII 1) BYTE1 ~ BYTE3 : Fixed Charactor (S T ,) 2) BYTE4, BYTE5...
  • Page 47: Ver6.4 Protocol

    RADIANQBIO INSTRUMENT www.radian21.com Transmission Data Form (INDICATOR -> PC) CODE BYTE1 BYTE2 BYTE3 BYTE4 BYTE5 BYTE6 BYTE7 BYTE8 ASCII CODE BYTE9 BYTE10 BYTE11 BYTE12 BYTE13 BYTE14 BYTE15 BYTE16 ASCII 1) BYTE1 ~ BYTE3 : Fixed Charactor (I D ,) 2) BYTE4, BYTE5 : Device number (1 ~ 99) 3) BYTE6 : Fixed Charactor (,)
  • Page 48 RADIANQBIO INSTRUMENT www.radian21.com ① Stream mode (F-40, ID Number setup value ‘000’) (Ex. Data +1234.5 transmieeion) CODE BYTE1 BYTE2 BYTE3 BYTE4 BYTE5 BYTE6 BYTE7 BYTE8 ASCII CODE BYTE9 BYTE10 BYTE11 BYTE12 BYTE13 BYTE14 BYTE15 BYTE16 ASCII 1) BYTE1, BYTE2 : DATA stable (S T) DATA unstable (U S) DATA overflow (O L) DATA underflow (U L)
  • Page 49 RADIANQBIO INSTRUMENT www.radian21.com CODE BYTE1 BYTE2 BYTE3 BYTE4 BYTE5 BYTE6 BYTE7 BYTE8 ASCII CODE BYTE9 BYTE10 BYTE11 BYTE12 BYTE13 BYTE14 BYTE15 BYTE16 ASCII 1) BYTE1 ~ BYTE3 : Fixed Charactor (I D 0) 2) BYTE4, BYTE5 : Device number (1 ~ 99) 3) BYTE6 : Fixed Charactor (,) 4) BYTE7~BYTE14...
  • Page 50: Modbus Rtu Protocol

    RADIANQBIO INSTRUMENT www.radian21.com Modbus RTU protocol (R/O : Read only, W/O : Write only. R/W : Read & Write) Address Func Description Value Type Format (Decimal) code Device Function Value 0000 0×04 F-00 Decimal Point 0 ~ 3 UNIT16 0001 0×04 F-01 Division...
  • Page 51 RADIANQBIO INSTRUMENT www.radian21.com Address Func Description Value Type Format (Decimal) code Device Configuration 0×0001 : ZERO 4000 0×06 External Input Command 0×0002 : Hold set UNIT16 0×0004 : Hold reset 4001 0×03 Relay Setpoint 1 -19999~+99999 INT32 4002 0×10 4003 0×03 Relay Setpoint 2 -19999~+99999...
  • Page 52 RADIANQBIO INSTRUMENT www.radian21.com X : No Function Address Func RI-10W RI-20W, Description RI-30W RI-148 (Decimal) code RI-50W 25W, 27W Decimal Point ○ ○ ○ 0000 0×04 F-00 Pulse/Circle (RI-30W) ○ 0001 0×04 F-01 Division ○ ○ ○ ○ 0002 0×04...
  • Page 53 RADIANQBIO INSTRUMENT www.radian21.com Address Func RI-10W RI-20W, Description RI-30W RI-148 (Decimal) code RI-50W 25W, 27W Device Configuration Zero : 0x0001 ○ ○ ○ 4000 0×06 Hold set : 0x0002 ○ ○ ○ ○ Hold reset : 0x0004 ○ ○ ○...