Overhead Cut-Off Device - Baxi Solo 2 PF Installation And Servicing Instruction

Wall mounted powered flue gas fired central heating unit
Table of Contents

Advertisement

8.0
Overheat Cut-oft Device – Page 34
8.1 Operation
1. The overheat cut-off device is of the manual reset type
and therefore It is important that the user knows how to
reset the control should it ever cut out.
NOTE: Cut-out is indicated by illumination of the neon
light on the control box.
2. Remove the lower door panel by following the
sequence of diagrams (Fig 87).
3. To reset the boiler - Turn the boiler thermostat control
knob fully anti-clockwise to the OFF position marked '0'
(Fig. 88). Wait ten seconds, turn the control knob
clockwise to the required thermostat setting, the red neon
goes out, the boiler will start automatically.
4. No adjustment to the gas controls or main thermostat
are required.
5. If the overheat thermostat drops out repeatedly, refer to
the fault finding chart at the rear of this booklet or consult a
competent service engineer.