Baxi Solo 2 PF Installation And Servicing Instruction page 12

Wall mounted powered flue gas fired central heating unit
Table of Contents

Advertisement

4.0
Site Requirements – Page 12
4.5 Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
NOTE: The ventilation label on the front of the outer
case MUST NOT BE REMOVED when the appliance is
installed in a compartment or cupboard.
2. B.S. 5440 Part 2 Clause 4.2 refers to room sealed
appliances installed in compartments. The Solo 2 PF will
run sufficiently cool without ventilation
4.6 Gas Supply (Fig. 13)
1. The gas installation should be in accordance with BS
6891.
2. The connection of the appliance is a RC ½ ( ½ in
BSPT internal) located at the rear of the gas cock.
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a
smaller diameter than the appliance gas connection.
4.7 Electrical Supply
External wiring must be correctly earthed, polarized and
in accordance with CURRENT I.E.E. WIRING
REGULATIONS.
The mains supply is 230V ~ 50Hz fused at 5k
NOTE: The method of connection to the electricity
supply must facilitate complete electrical isolation of
the appliance.
Connection may be made via a fused double-pole isolator
with a contact separation of a least 3mm in all poles and
serving the appliance and system controls only.
12