Placing the converter
The cabinet can be placed into its final position with an iron bar and a wooden piece at the
bottom edge of the cabinet. Place the wooden piece carefully to avoid damage to the cabinet
frame.
The cabinet has a back-to-back design. You cannot install it with the longer side against a
wall.
Install the converter in an upright vertical position.
Notes:
• Leave a 400 mm (16 in) clearance above the converter cabinet to allow pressure release
lids to open in an arc fault situation.
• Leave space at the side for the coolant pipes.
• You can adjust the height, for example, if the floor is uneven by using metal shims between
the cabinet frame and floor.
> 400 mm (16 in)
Mechanical installation 45