Connection Procedure - ABB ACS880-87LC-3200A Hardware Manual

Wind turbine converters
Table of Contents

Advertisement

Connection procedure

WARNING!
See and obey the safety instructions of the converter. If you ignore them, injury or
death, or damage to the equipment can occur.
WARNING!
Apply grease to stripped aluminum conductors before attaching them to non-coated
aluminum cable lugs. Obey the grease manufacturer's instructions.
Aluminum-aluminum contact can cause oxidation in the contact surfaces.
1. Grid connection terminals are located in the plinth of the converter. Fasten the grid cables
to the grid connection terminals. Connect the phase conductors to terminals L1, L2 and
L3. Tighten the conductors to 120 N·m (89 lbf·ft).
2. Connect ground conductors or cables to the cabinet PEN (ground) busbar.
3. Provide support for the connections whenever necessary.
4. Refit all shrouds (if any) removed earlier.
Electrical installation 63
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-87lc-3200a-7

Table of Contents