Miscellaneous; Cable Duct In The Floor Below The Cabinet; Electric Welding - ABB ACS880-87LC-3200A Hardware Manual

Wind turbine converters
Table of Contents

Advertisement

Miscellaneous

Cable duct in the floor below the cabinet

You can construct cable ducts below the cabinet. The duct width must not exceed 450 mm
(18 in). The cabinet weight lies on the 100 mm (4 in) wide sections in front, middle and back
which the floor must carry.
Prevent the cooling air flow from the cable duct to the cabinet by bottom plates. To ensure
the degree of protection for the cabinet use the original bottom plates delivered with the
converter. With user-defined cable entries, take care of the degree of protection, fire
protection and EMC compliance.

Electric welding

It is not recommended to fasten the cabinet by welding. If you must do it for some reason:
• Weld only the flat bar under the cabinet, never the cabinet frame itself.
• Clamp the welding electrode onto the flat bar about to be welded or to the next flat bar
of the cabinet (within 0.5 meters (1'6") of the welding point).
WARNING!
If the welding return wire is connected improperly, the welding circuit may damage
electronic circuits in the cabinet. The thickness of the zinc coating of the cabinet
frame is 100...200 micrometers; on the flat bars the coating is approximately
20 micrometers. Ensure that the welding fumes are not inhaled.
Mechanical installation 47