Mitsubishi Electric MCC-50A Installation And Instruction Manual page 15

Cloud system connection device
Table of Contents

Advertisement

5-4-2. Method 2: Installation using DIN rail
1. Have a metal control box ready.
2. Attach the supplied two DIN rail attachments to the MCC-50 with the supplied roundhead screws (M3 × 12). Tighten the screw
to a torque of 0.5 N·m.
3. Attach the supplied DIN rail auxiliary bracket to the MCC-50 with the supplied roundhead screws (M3 × 6). Tighten the screw
to a torque of 0.5 N·m.
4. Mount the DIN rail (not supplied) to the metal control box.
* Use a DIN rail of 35 mm (1-7/16 in) width.
Max. 200 (7-14/16)
Note
● To secure the strength, the screw pitch must be 200 mm (7-7/8 in) or less when DIN rail is mounted to the metal control box.
● The surface on which the MCC-50 will be installed needs to be strong enough to support its weight (1.7 kg (3-3/4 lbs) each).
● Do not install the MCC-50 where it may receive vibration.
● To avoid the contact of the DIN rail fixing screws with the DIN rail attachment, do not tighten the fixing screws at the shaded
areas in the figure below.
WT09836X01
MCC-50
DIN rail attachment
(supplied)
Roundhead screw (M3 × 12)
(supplied)
DIN rail auxiliary bracket
(supplied)
Roundhead screw (M3 × 6)
(supplied)
Unit: mm (in)
Do not tighten the fixing screw here.
15