4.

Troubleshooting (OP: Central Remote Controller)

" M1 "
4.1

PC Board Defect

M1
Remote
Controller
Display
Applicable
Central remote controller
Models
Method of
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction
Detection
Malfunction
When + polarity and - polarity are detected at the same time.
Decision
Conditions
Supposed
Causes
Troubleshooting
Replace the central remote controller.
Troubleshooting
Defect of central remote controller PC board