Initial Setup - YASKAWA VS mini V7 User Manual

Mechatrolink communications interface unit
Hide thumbs Also See for VS mini V7:
Table of Contents

Advertisement

6

Initial Setup

Before starting communications between the Inverter and the MECHATROLINK master, set
the following constants as required.
Constant
Name
No.
n003
Operation
Method Selec-
tion
n004
Frequency
Reference
Selection
* If running or stopping the Inverter from MECHATROLINK, set n003 to
3. If setting the frequency from MECHATROLINK, set n004 to 9. For
details, refer to the VS-606 V7 Series Instruction Manual (TOE-S606-
11).
Description
0: Digital Operator
1: Control-circuit terminal
2: MEMOBUS communications
3: Communications Card (optional)
0: Digital Operator
1: Frequency reference 1 (n024)
2: Control circuit terminal (0 V to 10 V)
3: Control circuit terminal (4 mA to 20 mA)
4: Control circuit terminal (0 mA to 20 mA)
5: Pulse train
6: MEMOBUS communications
7: Digital Operator circuit terminal (0 to 10 V)
8: Digital Operator circuit terminal (4 to 20 mA)
9: Communications Card (optional)
22
Default
0
0

Hide quick links: