Unit Keys - Quantech QTC3040T Installation Operation & Maintenance

Air-cooled scroll chiller with brazed plate heat exchanger style b 60 hz 4-12 fan 40 ton to 230 ton 140 kw to 800 kw
Table of Contents

Advertisement

FORM QTC3-NM1
ISSUE DATE 08/03/2022
Options Key
There are many user programmable options under the
OPTIONS key. The OPTIONS key is used to scroll
through the list of options by repeatedly pressing the
OPTIONS key. After the selected option has been dis-
played, the ↑ (UP) and ↓ (DOWN) arrow keys are then
used to change that particular option. After the option
is changed, the ENTER/ADV key must be pressed to
enter the data into memory.
Many of the OPTIONS displayed are
only programmable under the SERVICE
MODE and not under the OPTIONS key.
Options only programmable under the
SERVICE MODE are noted in the details
describing the option.
Figure 28 on page 142 shows the programmable op-
tions. Following are the displays in the order they ap-
pear:
Option 1 – Language
D I S P L A Y
E N G L I S H
English, Spanish, French, German, and Italian can be
programmed.
Option 2 – System Switches (two system
units only)
(Single System Display is similar)
S Y S
1
S W I T C H
S Y S
2
S W I T C H
QUANTECH

UNIT KEYS

OPTIONS
CLOCK
L A N G U A G E
O N
O N
00070VIP
This allows both systems to run.
or
S Y S
1
S W I T C H
S Y S
2
S W I T C H
This turns system 2 OFF.
S Y S
1
S W I T C H
S Y S
2
S W I T C H
This turns system 1 OFF.
or
S Y S
1
S W I T C H
S Y S
2
S W I T C H
This turns systems 1 and 2 OFF.
Turning a system OFF with its system
switch allows a pumpdown to be per-
formed before shutdown.
Option 3 – Chilled Liquid Cooling Type
C H I L L E D
W A T E R
The chilled liquid is water. The Cooling Setpoint can
be programmed from 40°F to 70°F (4.4°C to 21.1°C)
or
SECTION 7 – UNIT CONTROLS
O N
O F F
O F F
O N
O F F
O F F
L I Q U I D
137
7