Optional Printer Installation - Quantech QTC3040T Installation Operation & Maintenance

Air-cooled scroll chiller with brazed plate heat exchanger style b 60 hz 4-12 fan 40 ton to 230 ton 140 kw to 800 kw
Table of Contents

Advertisement

FORM QTC3-NM1
ISSUE DATE 08/03/2022
TABLE 34 - DATA LOGGING TO FLASH (CONT'D)
DATA
HEADER
NUMBER
TEXT
75
S1 Prop Cont In
76
S1 Int Cont In
77
S1 Der Cont In
78
S2 Full PID Index
79
S2 Dim PID Index
80
S2 Alg Ctrl Act
81
S2 Sheat Ex In
82
S2 Prop Cont In
83
S2 Int Cont In
84
S2 Der Cont In
85
S1 Thr Limit
86
S2 Thr Limit

OPTIONAL PRINTER INSTALLATION

The micro panel is capable of supplying a printout
of chiller conditions or fault shutdown information at
any given time. This allows operator and service per-
sonnel to obtain data and system status with the touch
of the keypad. In addition to manual print selection,
the micro panel will provide an automatic printout
whenever a fault occurs. Detailed explanation of the
print function is given under Print Key on page 122.
Parts
The following parts are required:
1. Printer.
2. Desk top calculator paper, 2.25 in. (5.7 cm) wide.
3. Twisted Pair Shielded Cable (minimum 3 conduc-
tor), #18 AWG stranded, 300 V minimum insula-
tion, 25 ft (7.62 m) maximum length.
4. One 25 pin Cannon connector and shell.
5. Cannon P/N DB-25P connector, or equivalent.
6. Cannon P/N DB-C2-J9 shell.
QUANTECH
UNIT
FORMAT
Sys 1 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
Sys 1 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
x
(0-1000000 in x10000 format)
Sys 1 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
Sys 2 CSHALG_FULL_PID_ACTIVE_INDEX
x
(0 = Disable, 1 = Active)
Sys 2 CSHALG_DIMINISHED_PID_ACTIVE_INDEX
x
(0 = Disable, 1 = Active)
Sys 2 CSHALG_ALGORITHM_CONTROL_ACTIVE
x
(0 = Disable, 1 = Enable)
Sys 2 CSHALG_SUPERHEAT_EXCURSIONS_INDEX
x
(0 – 255 in x1 format)
Sys 2 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
Sys 2 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
x
(0-1000000 in x10000 format)
Sys 2 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
%
x
Sys 1 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)
%
x
Sys 2 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)
SECTION 9 – SERVICE AND TROUBLESHOOTING
DATA
VALUE DESCRIPTION
Assembly and Wiring
All components should be assembled and wired as
shown in Figure 35. Strip the outside insulation back
several inches and individual wires about 3/8" (9.5
mm) to connect the cable at the Microboard. Do not
connect the shield at the printer-end of the cable.
Obtaining a Printout
A printout is obtained by pressing the PRINT key on
the keypad and then pressing either the OPER DATA
key or HISTORY key.