SECTION 3 – RIGGING, HANDLING AND STORAGE

MOVING THE CHILLER

Before moving the unit, ensure that the installation site
is suitable for installing the unit and is easily capable
of supporting the weight of the unit and all associated
services.
The unit must only be lifted by the base
frame at the points provided. Never move
the unit on rollers, or lift the unit using a
forklift truck.
Care should be taken to avoid damaging the condenser
cooling fins when moving the unit.
UNIT REMOVAL FROM SHIPPING
CONTAINER
1. Place a clevis pin into the holes provided at the
end of each base rail on the unit. Attach chains or
nylon straps through the clevis pins and hook onto
a suitable lift truck for pulling the unit out of the
container. (chain shown)
2. Slowly place tension on the chains or straps until
the unit begins to move and then slowly pull the
unit from the container. Be sure to pull straight so
the sides do not scrape the container.
3. Place a lifting fixture on the forks of the lift truck
and reattach the chain or strap. Slightly lift the
front of the unit to remove some weight from the
floor of the container. Continue pulling the unit
with an operator on each side to guide the lift
truck operator.
4. Pull the unit until the lifting locations are outside
of the container. Place 4 X 4 blocks of wood under
the base rails of the unit. Gently rest the unit on
the blocks and remove the chains and lift truck.
5. Attach lifting rigging from the crane and slowly
complete the removal from the container then lift
up and away.
32

LIFTING USING LUGS

Units are provided with lifting holes in the base frame
which accept the accessory lifting lug set as shown in
the figure below. The lugs (RH and LH) should be in-
serted into the respective holes in the base frame and
turned so that the spring loaded pin engages into the
hole and the flanges on the lug lock behind the hole.
The lugs should be attached to the cables/chains using
shackles or safety hooks.
CORRECT
LIFTING HOLE
LUG
IN BASE FRAME
FLANGE
LOCKING PIN
LUG
LOCKING
PIN

LIFTING USING SHACKLES

The shackles should be inserted into the respective
holes in the base frame and secured from the inside.
To avoid lifting chains hitting the chiller, use spreader
bars. Various methods of spreader bar arrangements
may be used, keeping in mind the intent is to keep the
unit stable and to keep the chains from hitting the chill-
er and causing damage.
Never lift the chiller using a forklift or by hooking to
the top rails. Use only the lifting holes provided.
Lifting Instructions are placed on a label on the chiller
and on the shipping bag.
FORM QTC3-NM1
ISSUE DATE 08/03/2022
INCORRECT
LUG
FLANGE
LOCKING PIN
LIFTING HOLE
IN BASE FRAME
FLANGE
QUANTECH