Unigas LMV5 Series Manual Of Installation - Use - Maintenance page 9

Microprocessor controlled gas - light oil burners
Table of Contents

Advertisement

How to read the burner "Performance curve"
To check if the burner is suitable for the boiler to which it must be instal-
lled, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h/860);
backpressure (data are available on the boiler ID plate or in the
user's manual).
Example:
Furnace input: 600kW
Backpressure: 4 mbar
In the "Performance curve" diagram, draw a vertical line matching the
furnace input value and an horizontal line matching the backpressure
value. The burner is suitable if the intersection point A is inside the per-
formance curve.
Data are referred to standard conditions: atmospheric pressure at 1013
mbar, ambient temperature at 15° C.
Checking the proper gas train size
To check the proper gas train size, it is necessary to the available
gas pressure value upstream the burner's gas valve. Then subtract
the backpressure. The result is called pgas. Draw a vertical line
matching the furnace input value (600kW, in the example), quoted
on the x-axis, as far as intercepitng the network pressure curve,
according to the installed gas train (DN65, in the example). From the
interception point, draw an horizontal line as far as matching, on the
y-axis, the value of pressure necessary to get the requested furnace
input. This value must be lower or equal to the pgas value, calcula-
ted before.
The values in the diagrams refer to natural gas with a calorific value of 8125 kcal/Stm
3
0.714 kg/Stm
.
The values in the diagrams refer to GPL with a calorific value of 22300 kcal/Stm
3
Stm
. When the calorific value and the density change, the pressure values should be adjusted accordingly.
8
7
6
5
4
3
2
1
0
-1
100
25
20
15
10
5
0
100
Natural gas pressure shown in diagram
Where:
Real gas pressure
Natural gas flow rate shown in diagram
Real gas flow rate
Natural gas density shown in diagram
Real gas density
9
PART I: SPECIFICATIONS
Campo di lavoro bruciatori
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
A
200
300
400
500
600
Power kW
Potenza kW
Rp 2" (50)
200
300
400
500
600
Power kW
Potenza / Output (kW)
3
(15°C, 1013 mbar) and a density of
3
(15°C, 1013 mbar) and a density of 2.14 kg/
700
800
900
DN65
DN65
700
800
900

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hrx92r-fgrHrx92-fgrHrx512-fgrHrx515-fgrHrx520-fgr

Table of Contents