Unigas LMV5 Series Manual Of Installation - Use - Maintenance page 33

Microprocessor controlled gas - light oil burners
Table of Contents

Advertisement

Lockout History
To visualise the Lockout History, choose the related item and press ENTER. The message will be:
alternating by an error message as:
To see the other Lockout History pages, press the arrow keys.
To exit the Lockout History pages, press ESC.
Setting the temperature/pressure set-point value
To set the temperature/pressure set-point value, that is the generator operating temperature/pressure; proceed as follows.
From the main page, enter the main menu by pressing the ESC key twice:
by means of the arrow keys, select "Params&Display", press ENTER: the system will ask you to enter the proper password
by means of the arrow keys, select "Access w-out pass" (access without password - user level), confirm by pressing ENTER.
The other levels require password reserved to the Technical Service, to the Manifacurer, etc.
The menu shown accessing without password is the following:
Choose "LoadController" and press ENTER: the following menu is shown:
1
10.08.07
C:71
D:00
Start No.
Load
0.0
No flame at end
of safety time
OperationalStat
Operation
ManualOperation
Params & Display
Access w-out PW
Access Serv
Access OEM
Access LS
BurnerControl
RatioControl
O2Contr./Guard.
LoadController
ControllerParam
Configuration
Adaption
SW Version
33
13.47
F:
12
88
Gas