Maintenance Timers And Counters; Cabinet; Cleaning The Interior Of The Cabinet - ABB ACS880-607LC Hardware Manual

3-phase dynamic brake units
Hide thumbs Also See for ACS880-607LC:
Table of Contents

Advertisement

Note:
Maintenance and component replacement intervals are based on the assumption
that the equipment is operated within the specified ratings and ambient
conditions. ABB recommends annual drive inspections to ensure the highest
reliability and optimum performance.
Long term operation near the specified maximum ratings or ambient conditions
may require shorter maintenance intervals for certain components. Consult your
local ABB Service representative for additional maintenance recommendations.

Maintenance timers and counters

The control program has maintenance timers and counters that can be configured to
generate a warning when a pre-defined limit is reached. Each timer/counter can be
set to monitor any parameter. This feature is especially useful as a service reminder.
For more information, see the firmware manual.

Cabinet

Cleaning the interior of the cabinet

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or
death, or damage to the equipment can occur. If you are not a qualified
electrical professional, do not do installation, commissioning or
maintenance work.
WARNING!
Use a vacuum cleaner with antistatic hose and nozzle, and wear a grounding
wristband. Using a normal vacuum cleaner creates static discharges which can
damage circuit boards.
1.
Stop the drive and do the steps in section
before you start the work.
2.
Open the cabinet door.
3.
Clean the interior of the cabinet. Use a vacuum cleaner and a soft brush.
4.
Clean the air inlets of the fans and air outlets of the modules (top).
5.
Clean the air inlet gratings (if any) on the door.
6.
Close the door.
Electrical safety precautions (page 35)
Maintenance 75

Advertisement

Table of Contents
loading

Table of Contents