102 Technical data

Altitude derating

At altitudes more than 1000 m (3281 ft) above sea level, the output current derating
is 1 percentage point for every added 100 m (328 ft). For example, the derating factor
for 1500 m (4921 ft) is 0.95. The maximum permitted installation altitude is given in
the technical data.
For a more accurate derating, use the DriveSize PC tool.

Frame sizes and modules used

Brake unit type
ACS880-607LC-...
U
= 690 V
N
0870-7
1300-7
1730-7
2600-7
3900-7
5200-7
6500-7

Fuses

DC fuses (IEC)

ACS880-607LC-...
U
= 690 V
N
0870-7
1300-7
1730-7
2600-7
3900-7
5200-7
6500-7
Inverter module(s) used
Frame
Qty
size
R8i
1
ACS880-104LC-0530A-7
R8i
1
ACS880-104LC-0850A-7
2×R8i
2
ACS880-104LC-0530A-7
2×R8i
2
ACS880-104LC-0850A-7
3×R8i
3
ACS880-104LC-0850A-7
4×R8i
4
ACS880-104LC-0850A-7
5×R8i
5
ACS880-104LC-0850A-7
Type
170M6500
2 x 170M6548
170M6500
2 x 170M6548
2 x 170M6548
2 x 170M6548
2 x 170M6548
Type
IEC
Data
1250 A, 1250 V
2 × 1000 A, 1100 V
1250 A, 1250 V
2 × 1000 A, 1100 V
2 × 1000 A, 1100 V
2 × 1000 A, 1100 V
2 × 1000 A, 1100 V
Qty
Qty
(per
(total)
module)
2
2
2 × 2
2 × 2
2
4
2 × 2
2 × 2 × 2
2 × 2
3 × 2 × 2
2 × 2
4 × 2 × 2
2 × 2
5 × 2 × 2