ALARM OPERATION
Alarms
1) Heater Break alarm: - If the current of the Heater < AMP SV
(unhealthy condition) then Relay turns ON and Upper
hbr
Display will show
, middle display will blink showing .
To manually turn off Relay, press ENT key 4 sec. Display will
hbr
continue showing
till the fault is rectified.
2) Cold start (CS) alarm: Relay is initially OFF. When PV >
Alarm SV, Relay turns ON. When PV < Alarm SV MINUS
HYS, Relay turns OFF.
ALARM:
RLY-ON
RLY-ON
RLY-OFF
ABSOLUTE LOW ALARM
RLY-OFF
RLY-ON
RLY-OFF
INBAND ALARM
RLY-ON
S.V
HYST
HYST
SET
RLY-OFF
RLY-ON
Low : 75
High : 125
High
RLY-ON
Low
ABSOLUTE OUTBAND ALARM
RLY-ON
h
RLY-OFF
LOW ALARM:
RLY-OFF
RLY-OFF
RLY-ON
OUTBAND ALARM
RLY-OFF
RLY-OFF
RLY-ON
High
RLY-OFF
Low
RLY-OFF
RLY-ON
High
RLY-OFF
Low
RLY-ON
RLY-OFF
HYST
S.V
RLY-ON
RLY-ON
RLY-ON
RLY-ON
High S.P
Low S.P
RLY-ON
Low : 75
High : 125
RLY-OFF
RLY-ON
RLY-OFF
RLY-ON
Low : 75
High : 125
RLY-OFF
RLY-ON