50
7.
Screw up the battery bracket and reconnect the battery cable A
and B
8.
Re-install the front panel back to UPS.
5
9.4 Testing New Batteries
For a battery test, please check:
The batteries must be fully charged.
The UPS must be in Normal mode with no active alarms.
Don't take on/off the load.
To test batteries:
1.
Connect the UPS to utility power for at least 48 hours to charge
the batteries.
2.
Press and hold the "I" button 1 second to start the battery test
on line mode or HE mode. The status display string shows
"TEST"
7