13.3.2 To set the setpoint
13.4 Date and time
13.4.1 About date and time
BRC1H81W+S7
Madoka wired remote controller
4P513690-1D – 2020.12
IF
The centralised controller or schedule
imposes a setpoint that exceeds the
regular +3°C/–3°C setpoint range.
Prerequisite: The active operation mode is either 'Cooling', 'Heating', or 'Auto'.
1 In the home screen, use
Result: The indoor unit changes its temperature setpoint.
Set the date and time for the indoor units connected to the controller.
Depending on daylight saving time settings, the date and time menu has the
following daylight saving time indicators:
The imposed setpoint becomes the new
upper/lower limit of the +3°C/–3°C
range, and the whole range shifts in
relation to this new limit.
Example: the reference setpoint is set
to 25°C, yielding the following setpoint
range:
If the centralised controller or schedule
changes the setpoint to 21°C, which is
below the range, then "21°C" becomes
the new lower limit, and the range
shifts in relation to this new limit.
and
to adjust the setpoint.
13
Operation
|
THEN
28°C
+3°C
25°C
-3°C
22°C
28°C
+3°C
25°C
-3°C
22°C
21°C
27°C
+3°C
24°C
-3°C
21°C
Installer and user reference guide
57