15
|
About the app
Precautions when performing a test operation
To perform a test operation
Installer and user reference guide
120
INFORMATION
Also see the installation manual of the indoor unit and outdoor unit.
CAUTION
Before starting up the system, make sure:
▪
The indoor and outdoor unit wiring is completed.
▪
The switch box covers of the indoor and outdoor units are closed.
NOTICE
Be sure to turn ON the power 6 hours before operation in order to have power
running to the crankcase heater and to protect the compressor.
INFORMATION
After the installation of the refrigerant piping, drain piping, and electrical wiring,
make sure to clean the inside of the indoor unit, as well as the decoration panel.
1 Confirm that the indoor unit gas and liquid stop valves are open.
INFORMATION
It is possible that the pressure inside the refrigerant circuit does not rise, despite the
opened stop valve. This can be due to the expansion valve (or the like) blocking the
refrigerant, and does not obstruct the test run.
2 Open the Madoka Assistant app.
3 Navigate to the operation screen of the controller that is connected to the
indoor unit(s) on which you want to perform a test run.
4 In the operation screen, set the operation mode to Cooling.
5 Go to the "Unit settings" menu (upper right corner of the operation screen).
Result: You are in the "Unit settings" menu.
6 In the "Maintenance field", tap "Test operation".
Result: You are in the "Test operation" menu.
7 Tap "Start test operation".
Result: The indoor unit(s) enter test operation mode, during which normal
operation is not possible.
8 Return to the operation screen.
9 Tap "Vertical airflow direction".
10 Tap "Fixed".
11 Cycle through the five fixed airflow directions, and confirm if the indoor unit
flaps behave correspondingly.
12 Return to the "Test operation" menu.
13 Tap "Stop test operation".
Result: The indoor units leave test operation mode. Normal operation is
possible again.
BRC1H81W+S7
Madoka wired remote controller
4P513690-1D – 2020.12