Single and Dual setpoint mode

19. Single and Dual setpoint mode
NOTE
● When a centralized controller is connected, the remote controller is forced to single setpoint
mode. It is not possible to change to dual setpoint mode.
● Switch between Single setpoint mode and Dual setpoint mode
● Single setpoint mode is set by selecting "Single SP"
● Dual setpoint mode is set by selecting "0°C" – "8°C"
19-1
Press and hold the Cancel button for
4 seconds or longer. The Service
Settings menu is displayed.
19-2
Select
Min Setpoints Differential
and press the Menu/Enter button.
The "Min Setpoints Differential"
screen is displayed.
19-3
Select "None", "Single Sp" or
"0°C" – "8°C" by using the
Down) buttons.
19-4
Press the Menu/Enter button. The
confirmation screen is displayed.
19-5
Select
Yes
and press the Menu/
Enter button. The settings are
confirmed and the Service Settings
menu returns.
19-6
Press the Cancel button once. The
remote controller restarts and the
Basic screen returns.
Installer reference guide
43
<Basic screen>
19-1
Cool
<Service Settings>
19-2
Service Settings
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
External Input Interlock
Return
19-3
Min Setpoints Differential
(Up/
19-4
Min Setpoints Differential
Return
19-5
Min Setpoints Differential
Save the settings?
Yes
Return
<Service Settings>
Set to
28
Press and hold the Cancel
°C
button for 4 seconds or
longer while the backlight
1/3
Press the Menu/Enter
Setting
Single Sp
Press the Menu/Enter
Setting
No
Press the Menu/Enter
Setting
4P419250-1 – 2015.10
is lit.
button.
button.
button.
BRC1E53