Diagnostics and Troubleshoo...
Symptom
Possible cause
Acoustic noise
Resonances, e.g., in the
or vibration
motor/fan system
(e.g., a fan
blade is
making noise
or vibrations
at certain
frequencies)
Table 7.5 Troubleshooting
MG11AK22
Instruction Manual
Test
Bypass critical frequencies by using
parameters in parameter group 4-6* Speed
Bypass.
Turn off overmodulation in 14-03 Overmo-
dulation.
Change switching pattern and frequency in
parameter group 14-0* Inverter Switching.
Increase Resonance Dampening in
1-64 Resonance Dampening.
Danfoss A/S © 03/2015 All rights reserved.
Solution
Check if noise and/or vibration have been
reduced to an acceptable limit.