Danfoss VLT HVAC Drive FC 102 Instruction Manual page 70

Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Specifications
525–600 V
Enclosure
type
A3
B3
B4
C3
C4
A5
B1
8
8
B2
C1
C2
Table 8.14 525–600 V, Enclosure Types A, B and C
525–690 V
Enclosure
type
A3
B2/B4
B4/C2
C2/C3
C2
Table 8.15 525–690 V, Enclosure Types A, B and C
66
Power (hp [kW])
Recommended
fuse size
5.5–7.5
gG-10 (7.5 [5.5])
gG-16 (10 [7.5])
15–24 [11–18]
gG-25 (15 [11])
gG-32 (20–25 [15–18])
30–50 [22–37]
gG-40 (30 [22])
gG-50 (40 [30])
gG-63 (50 [37])
60–75 [45–55]
gG-63 (60 [45])
gG-100 (75 [55])
100–125 [75–90]
aR-160 (100 [75])
aR-200 (125 [90])
1.5–10 [1.1–7.5]
gG-10 (1.5–7.5 [1.1–5.5])
gG-16 (10 [7.5])
15–24 [11–18]
gG-25 (15 [11])
gG-32 (20 [15])
gG-40 (25 [18.5])
30–40 [22–30]
gG-50 (30 [22])
gG-63 (40 [30])
50–75 [37–55]
gG-63 (50 [37])
gG-100 (60 [45])
aR-160 (75 [55])
100–125 [75–90]
aR-200 (100–125 [75–90])
Power (hp [kW])
Recommended
fuse size
1.5 [1.1]
gG-6
2 [1.5]
gG-6
3 [2.2]
gG-6
4 [3]
gG-10
5 [4]
gG-10
7.5 [5.5]
gG-16
10 [7.5]
gG-16
15 [11]
gG-25 (15 [11])
20 [15]
gG-32 (20 [15])
24 [18]
gG-32 (24 [18])
30 [22]
gG-40 (30 [22])
40 [30]
gG-63 (40 [30])
50 [37]
gG-63 (50 [37])
60 [45]
gG-80 (60 [45])
75 [55]
gG-100 (75 [55])
100 [75]
gG-125 (100 [75])
Danfoss A/S © 03/2015 All rights reserved.
®
VLT
HVAC Drive FC 102
Recommended
max. fuse size
gG-32
gG-63
gG-125
gG-150
aR-250
gG-32
gG-80
gG-100
gG-160 (50–60 [37–45])
aR-250 (75 [55])
aR-250
Recommended
max. fuse size
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-63
gG-80 (40 [30])
gG-100 (50 [37])
gG-125 (60 [45])
gG-160 (75–100 [55–75])
Recommended circuit
Max. trip level [A]
breaker (Moeller)
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
Recommended circuit
Max. trip level [A]
breaker (Moeller)
PKZM0-16
-
-
-
25
50
100
150
250
25
63
100
160
250
16
-
-
-
MG11AK22

Advertisement

Table of Contents
loading

Table of Contents