Danfoss VLT HVAC Drive FC 102 Instruction Manual page 68

Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Specifications
8.8.1 CE Compliance
200–240 V
Enclosure
type
A2
A3
B3
B4
C3
C4
A4
8
8
A5
B1
B2
C1
C2
Table 8.12 200–240 V, Enclosure Types A, B and C
64
Power (hp [kW])
Recommended
fuse size
1.5–3 [1.1–2.2]
gG-10 (1.5–2 [1.1–1.5])
gG-16 (3 [2.2])
4–5 [3.0–3.7]
gG-16 (4 [3])
gG-20 (5 [3.7])
7.5–15 [5.5–11]
gG-25 (7.5–10 [5.5–7.5])
gG-32 (15 [11])
20–24 [15–18]
gG-50 (20 [15])
gG-63 (25 [18])
30–40 [22–30]
gG-80 (30 [22])
aR-125 (40 [30])
50–60 [37-45]
aR-160 (50 [37])
aR-200 (60 [45])
1.5–3 [1.1–2.2]
gG-10 (1.5–2 [1.1–1.5])
gG-16 (3 [2.2])
0.25–3.7
gG-10 (0.34–2 [0.25–1.5])
gG-16 (3–4 [2.2–3])
gG-20 (5 [3.7])
7.5–15 [5.5–11]
gG-25 (7.5 [5.5])
gG-32 (10–15 [7.5–11])
20 [15]
gG-50
24–40 [18–30]
gG-63 (25 [18.5])
gG-80 (30 [22])
gG-100 (40 [30])
50–60 [37–45]
aR-160 (50 [37])
aR-200 (60 [45])
Danfoss A/S © 03/2015 All rights reserved.
®
VLT
HVAC Drive FC 102
Recommended
max. fuse size
gG-25
gG-32
gG-63
gG-125
gG-150 (30 [22])
aR-160 (40 [30])
aR-200 (50 [37])
aR-250 (60 [45])
gG-32
gG-32
gG-80
gG-100
gG-160 (25–30 [18.5–22])
aR-160 (40 [30])
aR-200 (50 [37])
aR-250 (60 [45])
Recommended circuit
Max. trip level [A]
breaker (Moeller)
PKZM0-25
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
25
25
50
100
150
250
25
25
63
100
160
250
MG11AK22