Danfoss VLT HVAC Drive FC 102 Instruction Manual page 38

Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Application Set-up Examples
6.1.5 Motor Thermistor
CAUTION
THERMISTOR INSULATION
Risk of equipment damage exists.
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
VLT
6
6
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.10 Motor Thermistor
34
®
VLT
HVAC Drive FC 102
Parameters
Function
Setting
1-90 Motor
[2]
Thermal
Thermistor
Protection
trip
1-93 Thermistor
[1] Analog
Source
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1] Thermistor
warning.
D IN 37 is an option.
Danfoss A/S © 03/2015 All rights reserved.
MG11AK22