Danfoss VLT HVAC Drive FC 102 Instruction Manual page 18

Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Electrical Installation
4
4
1
9
1
PLC
2
Adjustable frequency drive
3
Output contactor
4
Grounding rail (PE)
5
Cable insulation (stripped)
Figure 4.2 EMC-compliant Electrical Connection
NOTICE!
EMC INTERFERENCE
Run cables for input power, motor wiring and control wiring in three separate metallic conduits. Failure to isolate power,
motor and control cables can result in unintended behavior or reduced performance. Minimum 7.9 in [200 mm]
clearance between power, motor and control cables is required.
14
®
VLT
HVAC Drive FC 102
2
10
L1
L2
L3
PE
8
Danfoss A/S © 03/2015 All rights reserved.
11
6
6
Cable connector
7
Motor, 3-phase and PE
8
Line power, 3-phase and reinforced PE
9
Control wiring
10
Equalizing min. 0.025 in
3
4
5
u
v
w
PE
7
2
2
[16 mm
]
MG11AK22

Advertisement