Programming Example: Linking Two Closing Windows Over Midnight - Bosch D9412GV3 Program Entry Manual

Table of Contents

Advertisement

D9412GV3/D7412GV3 | Program Entry Guide | 4.0
If the window must activate on the same day as it is
programmed, reboot the control panel to activate the
window immediately.
W# Close Window Start
Default:
00: 00
Selection:
HH:MM (hours and minutes)
Enter the time that you want the control panel to start
the Closing Window. The window goes into effect at
the beginning of the minute.
00:00 is midnight, 23:59 is 11:59 PM. Make entries
using a 24-hour clock (for example, 7:00 AM is
entered as 07:00, 2:45 PM is entered as 14:45).
This program item is one of three required to create a
Closing Window. To program a Closing Window,
Close Early Begin and Close Window Stop must also
be programmed.
If the area is not armed when the Close Window Start
time comes, a warning tone sounds and PLEASE
CLOSE NOW appears at the keypad. To temporarily
silence the tone, press the [ESC] key on the keypad.
The warning tone restarts in 10 min if the area is not
armed.
Refer to the W# Close Early Begin prompt in this
section for explanations of report features.
Table 32: Programming Example: Linking Two Closing Windows over Midnight
W
#
Day of Week
1
S M T W T F S
2
S M T W T F S
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Open
Early
Early
Begin
Start
Stop
Begin
22 : 00
00 : 00
Get other manuals https://www.bkmanuals.com
Schedules (Skeds)
W# Close Window Stop
Default:
00: 00
Selection:
HH:MM (hours and minutes)
Enter the time that you want the control panel to end
the Closing Window. The window stops at the end of
the minute.
00:00 is midnight, 23:59 is 11:59 PM. Make entries
using a 24-hour clock (for example, 7:00 AM is
entered as 07:00, 2:45 PM is entered as 14:45).
This program item is one of three required to create a
Closing Window. To program a Closing Window,
Close Early Begin and Close Window Start must also
be programmed.
If the area is not armed by the time the Close
Window Stop time expires, the control panel
generates a Fail to Close Report if enabled in Fail To
Close.
Closing Reports generated between the Close
Window Start time and Close Window Stop time can
be suppressed by programming Disable O/C in
Window as Yes. Refer to the W# Close Early Begin
prompt for other explanations of report features.
Do not use a time of 23:59 as a window stop time
unless the window continues on the next day at
00:00. Fail to Close Reports are not sent, and the
Auto Close feature does not work for windows that
stop at 23:59.
Do not program a single window to cross the
midnight boundary. The window stop time must be
later than the window start time. To program a
window that effectively crosses the midnight
boundary, you must program two windows.
For example, to program windows for an area that
closes between 11:30 PM and 12:30 AM, five days a
week, use two windows as shown in Table 32.
Close
eXcept
On
Start
Stop
Holiday
23 : 30
23 : 59
Yes
No
00 : 00
00 : 30
Yes
No
EN | 109
Holiday
Index
Area(s)
1 2 3 4
1 2 3 4 5 6 7 8
1 2 3 4
1 2 3 4 5 6 7 8