Electrical Connection - GEM R639 eSyStep Operating Instructions Manual

Motorized diaphragm valve
Hide thumbs Also See for R639 eSyStep:
Table of Contents

Advertisement

6.9 Behaviour in the event of an error
Function:
Error position:

7 Electrical connection

Appropriate cable socket/appropriate mating connector
▶ The appropriate connector is included for X1.
7.1 Position of the connectors
X1
7.2 Electrical connection
7.2.1 Connection X1
2
1
3
6
4
5
7-pin plug, Binder, type 693
Pin
1
Uv, 24 V DC supply voltage
2
GND
3
Digital input 1
4
Digital input 2
5
Digital input/output
6
Digital output, IO-Link
7
n.c.
www.gemu-group.com
In the event of an error the valve moves to the error position.
Notes: Moving to the error position is only possible with full power supply. This behaviour is not a
safety position. The valve must be operated with a GEMÜ 1571 emergency power supply module
(see accessories) to ensure the function in case of voltage loss.
Closed, open or hold (adjustable via IO-Link).
Signal name
NOTICE
15 / 71
7 Electrical connection
GEMÜ R639 eSyStep
OPEN / CLOSE (Code AE)