• Each joint in the assembly must be fastened with at least three screws.
• The assembly must have allowance for expansion: elbows in assemblies allow for expansion; straight
assemblies should include an inspection wrap with one end unfastened, or a telescopic section.
• Minimum upward slope towards the chimney: 20 mm/m (1/4 in/ft.).
• One end of the assembly must be securely fastened to the flue collar with 3 sheet metal screws and
the other end securely fastened to the chimney.
• There must be provision for cleaning of the pipes, either through a clean out or by removal of the
pipe assembly. Removal of the assembly should not require that the stove be moved.
• The male ends of the sections must be oriented towards the appliance so that falling dust and
condensation stay inside the pipe.
• A flue pipe must never pass through a combustible floor or ceiling or through an attic, roof space,
closet or concealed space.
• Where passage through a wall or partition of combustible construction is desired, the installation shall
conform to CAN/CSA-B365, Installation Code for Solid-Fuel-Burning Appliances and Equipment.
• A straight up connector assembly needs either a telescopic length or an inspection wrap (pipe
coupler) to allow it to be assembled and disassembled without moving the stove.
• A straight flue pipe assembly offers the least restriction to gas flow and results in stronger draft.
Straight assemblies also need less maintenance because there are no corners to collect creosote.
• The chimney connector must be in good condition.