8.2.2 Factory-Built Metal Chimneys in Mobile Homes
For use in a mobile home, this stove is to be
connected to a 6" double wall factory built chimney
pipe conforming to UCL-S629, standards for 650°C
Factory-built chimney. The total length of the flue
system should be at least 12 feet including elbows,
from the top of the stove.
To maintain an effective vapour barrier, insulation
and waterproof at the chimney and outside flue pipe,
a roof flashing must be installed and sealed with
silicone adhesive.
8.2.3 Masonry Chimneys
The stove may also be connected to a masonry
chimney, provided the chimney complies with the
construction rules found in the building code enforced
locally. The chimney must have either a clay liner or
a suitably listed stainless steel liner. If the masonry
chimney has a square or rectangular liner that is
larger in cross sectional area than a round 6" flue, it
should be relined with a suitably listed 6" stainless
steel liner. Do not downsize the flue to less than 6"
unless the venting system is straight and exceeds 25
feet in height. When passing through a combustible
wall, the use of an insulated listed thimble is required.