There are the following possibilities for project transfer into the CPU:
n
Transfer via MPI/PROFIBUS
n
Transfer via Ethernet
n
Transfer via memory card
For transfer via MPI/PROFIBUS the CPU has the following interface:
n
X2: MPI interface
n
X3: PROFIBUS interface
The structure of a MPI net is electrically identical with the structure of a PROFIBUS net.
This means the same rules are valid and you use the same components for the build-up.
The single participants are connected with each other via bus interface plugs and
PROFIBUS cables. Per default the MPI net runs with 187.5kbaud. Yaskawa CPUs are
delivered with MPI address 2.
The MPI programming cables are available at Yaskawa in different variants. The cables
provide a RS232 res. USB plug for the PC and a bus enabled RS485 plug for the CPU.
Due to the RS485 connection you may plug the MPI programming cables directly to an
already plugged plug on the RS485 jack. Every bus participant identifies itself at the bus
with an unique address, in the course of the address 0 is reserved for programming
devices.
A cable has to be terminated with its surge impedance. For this you switch on the termi-
nating resistor at the first and the last participant of a network or a segment. Please make
sure that the participants with the activated terminating resistors are always power sup-
plied. Otherwise it may cause interferences on the bus.
1.
Connect your PC to the MPI jack of your CPU via a MPI programming cable.
2.
Load your project in the Siemens SIMATIC Manager.
3.
Choose in the menu 'Options è Set PG/PC interface'.
4.
Select in the according list the "PC Adapter (MPI)"; if appropriate you have to add it
first, then click on [Properties].