System 300S

6.3 Deployment of RS485 interface for PtP

Activate RS485 to PtP
operation
Requirements
Installation of the
SPEEDBUS.GSD
HB140 | CPU | 315-4PN23 | en | 18-02
Per default, the RS485 interface is deactivated. Via hardware configuration the RS485
interfaces may be switched to PtP operation (point to point) via the parameter Function
RS485 of the Properties.
Since the VIPA specific CPU parameters may be set, the installation of the
SPEEDBUS.GSD from VIPA in the hardware catalog is necessary. The CPU may be con-
figured in a PROFIBUS master system and the appropriate parameters may be set after
installation.
The GSD (Geräte-Stamm-Datei) is online available in the following language versions.
Further language versions are available on inquires:
Name
SPEEDBUS.GSD
SPEEDBUS.GSG
SPEEDBUS.GSE
The GSD files may be found at www.yaskawa.eu.com at the service area.
The integration of the SPEEDBUS.GSD takes place with the following proceeding:
1.
Go to the service area of www.yaskawa.eu.com.
2.
Load from the download area at 'Config files è PROFIBUS' the according file for
your System 300S.
3.
Extract the file to your work directory.
4.
Start the hardware configurator from Siemens.
5.
Close every project.
6.
Select 'Options è Install new GSD-file'.
7.
Navigate to the directory VIPA_System_300S and select SPEEDBUS.GSD an.
ð The SPEED7 CPUs and modules of the System 300S from Yaskawa may now
be found in the hardware catalog at PROFIBUS-DP / Additional field devices /
I/O / VIPA_SPEEDBUS.
Deployment PtP communication
Deployment of RS485 interface for PtP
Language
German (default)
German
English
77