Fast Introduction - YASKAWA SPEED7 300S+ CPU 315PN Manual

Table of Contents

Advertisement

+
System 300S

9.4 Fast introduction

Overview
Steps of configuration
HB140 | CPU | 315-4PN23 | en | 18-02
Range of functions
Please regard that the PROFINET IO controller supports only the
PROFINET functions, which are described in this manual, even if the Sie-
mens CPU, which is used for configuration, offers further functions! To
use some described PROFINET functions, it is necessary to deploy
another Siemens CPU for configuration. Here, however, is pointed to
explicitly.
At the first commissioning respectively after an overall reset with PowerON again of the
CPU, the Ethernet PG/OP channel and the PROFINET IO controller have no IP address.
These are only reachable by its MAC address. IP address parameters may be assigned
to the corresponding component by means of the MAC addresses, which may be found
on labels beneath the front flap with the sequence 1. address PG/OP channel and
beneath address of the PROFINET IO controller. The assignment takes place directly via
the hardware configuration of the Siemens SIMATIC manager.
The configuration of the PROFINET IO controller for PROFINET communication should
be done by the following procedure:
1.
Commissioning and Initialization (assignment IP address data)
2.
Hardware configuration - CPU
3.
Configuration PROFINET IO controller
4.
Configuration PROFINET IO device
5.
Transfer of the entire project to the CPU
To be compatible with the Siemens SIMATIC Manager the CPU
315-4PN23 from VIPA is to be configured as
CPU 315-2 PN/DP (6ES7 315-2EH14-0AB0 V3.2)!
The Ethernet PG/OP channel of the CPU 315-4PN23 is to be configured
as 1. module as CP343-1 (343-1EX11) from Siemens after the really
plugged modules at the standard bus.
Deployment Ethernet communication - PROFINET
Fast introduction
125