Deployment

Hardware configuration

5.2 Hardware configuration
Overview
Project engineering
28
n
The description here refers to modules that are at the same bus together with the
CPU. In order to address the installed modules individually, specific addresses in the
CPU have to be assigned to them. The allocation of addresses and the configuration
of the installed modules is a function of the Siemens SIMATIC manager.
n
Here navigate within the hardware catalog to the according CP and place it at the
S7-300 station.
1.
Start the Siemens SIMATIC Manager.
2.
Swap to the hardware configurator.
3.
Place a profile rail via drag&drop from the hardware catalog to the project window.
4.
Project the CPU and the corresponding modules.
Place the corresponding modules via drag&drop from the hardware catalog to the
corresponding slot of the profile rail.
5.
To project the VIPA CP 341-1CH01 the Siemens CP 341 (6ES7 341-1CH01-0AE0)
at the according slot is to be used.
6.
Adjust via the CP "properties" the transmission protocol and the protocol specific
parameters (see protocol parameters). Note the address from which the CP is
embedded. This value is necessary for the integration in your user program.
Ä Chap. 5.3 'Communication with the user program' page 31
7.
Save and translate your project and transfer it to the CPU.
VIPA System 300S
HB130 | CP | 341-1CH01 | en | 18-40