Stability Of The Busbar Differential Protection - ABB Relion 670 Series Commissioning Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 372-UUS Rev. K
16.
Repeat the steps from
Test the operation of both differential protection function ZA and ZB simultaneously
17.
Make sure the current from this current input is included into both measuring zones ZA and ZB
simultaneously.
Check the value for the configuration parameter ZoneSel of the CTx, and
18.
Make sure that the dedicated binary output ACTIVE from the Zone Interconnection block has the
logical value one.
19.
Repeat the steps from
10.3.1.3

Stability of the busbar differential protection

For stability test one current input shall always be used as a reference input. The reference current input
then shall be tested for stability against all other current inputs in the IED. It is recommended to use
current input CT1 as the reference current input. The typical connection between the three-phase current
test set and the IED for this type of tests is shown in Figure 13.
REB 670
ANSI01000113-2 V1 EN-US
Figure 13:
The connections are shown for phase A only. Similar connection shall be used for testing phase B and C
also.
Busbar protection REB670
Commissioning manual
de-energize the binary input CTRLZA and energize the binary input CTRLZB, if the value of
ZoneSel is CtrlIncludes,
energize the binary input CTRLZA and de-energize binary input CTRLZB, if the value of
ZoneSel is CtrlExcludes
go directly to the next step, otherwise,
5
to
14
for ZB
energize both the binary inputs CTRLZA and CTRLZB, if the value of ZoneSel is CtrlIncludes,
de-energize both the binary inputs CTRLZA and CTRLZB, If the value of ZoneSel is
CtrlExcludes,
go directly to the next step, otherwise
5
to
14
for both ZA and ZB.
REB 670
REB 670
Typical test connection for CT1 and CTx current inputs of the phase A when test
switch is delivered together with the one-phase IED
© 2017 - 2022 Hitachi Energy. All rights reserved
3
4
B
1
2
A
3
4
B
1
2
A
3
1
1
15
6
H
13
14
G
1
15
6
H
13
14
G
15
13
Testing functionality by secondary injection
3-Ph current
Test Set
A
B
C
N
IA
IB
4
B
2
A
1
6
H
14
G
en01000113_2_ansi.vsd
Section 10
SEMOD65867-3 v5
73