Differential Protection - ABB RELION 650 Series Product Manual

Transformer protection
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Transformer protection RET650 2.1 IEC
Table 4. Local HMI functions
IEC 61850 or function
ANSI
name
LHMICTRL
LANGUAGE
SCREEN
FNKEYTY1–FNKEYTY5
FNKEYMD1–FNKEYMD5
LEDGEN
OPENCLOSE_LED
GRP1_LED1–
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15

3. Differential protection

Transformer differential protection T3WPDIF
The Transformer differential protection is provided with
internal CT ratio matching, vector group compensation
and settable zero sequence current elimination.
The function can be provided with up to six three-phase
sets of current inputs if enough HW is available. All
current inputs are provided with percentage bias
restraint features, making the IED suitable for two- or
three-winding transformer in multi-breaker station
arrangements.
12
Description
Local HMI signals
Local human machine language
Local HMI Local human machine screen behavior
Parameter setting function for HMI in PCM600
General LED indication part for LHMI
LHMI LEDs for open and close keys
Basic part for CP HW LED indication module
M16104-3 v17
Two-winding applications
two-winding power
transformer
xx05000048.vsd
IEC05000048 V1 EN-US
two-winding power
transformer with
unconnected delta
xx05000049.vsd
tertiary winding
IEC05000049 V1 EN-US
two-winding power
transformer with
two circuit breakers
xx05000050.vsd
and two CT-sets on
IEC05000050 V1 EN-US
one side
two-winding power
transformer with
two circuit breakers
and two CT-sets on
both sides
xx05000051.vsd
IEC05000051 V1 EN-US
Three-winding applications
three-winding
power transformer
with all three
windings connected
xx05000052.vsd
IEC05000052 V1 EN-US
1MRK 504 161-BEN C
ABB