1MRS757656 A
2.3.5.34
Table 60:
LD0.FRPFRQ6 Frequency protection (6)
IEC 61850 name
LD0.FRPTRC6
.Str.general
LD0.FRPTOF6
.Op.general
LD0.FRPTUF6
.Op.general
LD0.FRPFRC6
.Op.general
2.3.5.35
Table 61:
LD0.JAMPTOC1 Stalled motor protection
IEC 61850 name
LD0.JAMPTOC1
.Op.general
2.3.5.36
Table 62:
LD0.MPDIF1 Motor differential protection (1)
IEC 61850 name
LD0.MPDIF1
.Op.general
2.3.5.37
Table 63:
LD0.MPTTR1 Motor thermal overload protection
IEC 61850 name
LD0.MPTTR1
.AlmThm.general
.Op.general
.StrInh.general
REM620
Point List Manual
LD0.FRPFRQ6 Frequency protection (6)
SA name
START
OPR_OFRQ
OPR_UFRQ
OPR_FRG
LD0.JAMPTOC1 Stalled motor protection
SA name
OPERATE
LD0.MPDIF1 Motor differential protection (1)
SA name
OPERATE
LD0.MPTTR1 Motor thermal overload protection
SA name
ALARM
OPERATE
BLK_RESTART
Description
Stage start
Overfrequency
-Operate
Underfrequency
-Operate
Frequency gradient
-Operate
Description
Stage operate
Description
Stage operate
Description
Thermal alarm
Thermal operate
Block restart
Section 2
DNP3 data mappings
Values
1=Start
1=Operate
1=Operate
1=Operate
Values
1=Operate
Values
1 = Operate
Values
1=Alarm
1=Operate
1=Restart
33