Section 13
Troubleshooting
Indicated result
(Protocol name) Fail
(I/O module name)
Ready
(I/O module name) Fail
13.2
Fault tracing
13.2.1
Internal fault indications
If an internal fault has occurred, the local HMI displays information under Main menu /Diagnostics/IED
status /General
Under the Diagnostics menus, indications of a possible internal failure (serious fault) or internal warning
(minor problem) are listed.
Indications regarding the faulty unit are outlined in table 21.
Table 21:
HMI Signal Name:
INT Fail
INT Warning
ADMnn
BIMnn
BOMn
IOMn
MIMn
RTC
Time Sync
Table continues on next page
158
Possible reason
Protocol has failed.
No problem detected.
I/O modules has failed.
Self-supervision signals on the local HMI
Status
OFF / ON
OFF / ON
READY / FAIL
READY / FAIL
READY / FAIL
READY / FAIL
READY / FAIL
READY / FAIL
READY / FAIL
© 2017 - 2022 Hitachi Energy. All rights reserved
Proposed action
None.
Check that the I/O module has been configured and connected to
the IOP1- block.
If the problem persists, contact your Hitachi Power grids
representative for service.
Description
This signal will be active if one or more
of the following internal signals are
active; INT--LMDERROR, INT--
WATCHDOG, INT--APPERROR, INT--
RTEERROR, or any of the HW
dependent signals
This signal will be active if one or more
of the following internal signals are
active; INT--RTCERROR, INT--
IEC61850ERROR, INT--
TIMESYNCHERROR
Analog input module n failed. Signal
activation will reset the IED
BIM error. Binary input module Error
status. Signal activation will reset the
IED
BOM error. Binary output module Error
status.
IOM-error. Input/Output Module Error
status.
mA input module MIM1 failed. Signal
activation will reset the IED
This signal will be active when there is a
hardware error with the real time clock.
This signal will be active when the
source of the time synchronization is
lost, or when the time system has to
make a time reset.
1MRK 505 372-UUS Rev. K
IP8765-1 v1
M11763-2 v7
Busbar protection REB670
Commissioning manual