Section 10
Testing functionality by secondary injection
1.
Connect the test set for injection of voltage and current corresponding to the mode to be used in
the application. If a three-phase test set is available this could be used for all the modes. If a single-
phase current/voltage test set is available the test set should be connected to a selected input for
one-phase current and voltage.
Table 18:
Set value: Mode
A, B, C
Arone
PosSeq
AB
BC
CA
A
B
C
2.
Adjust the injected current and voltage to the set values in % of IBase and VBase (converted to
secondary current and voltage). The angle between the injected current and voltage shall be set
equal to the set direction Angle1, angle for stage 1 (equal to 0° for low forward power protection
94
Calculation modes
Formula used for complex power calculation
=
S
V
A
EQUATION2055 V1 EN-US
=
S
V
AB
EQUATION2056-ANSI V1 EN-US
= ×
S
3
V
EQUATION2057-ANSI V1 EN-US
=
S
V
AB
EQUATION2058-ANSI V1 EN-US
=
S
V
BC
EQUATION2059-ANSI V1 EN-US
=
S
V
CA
EQUATION2060-ANSI V1 EN-US
= ×
S
3
V
EQUATION2061-ANSI V1 EN-US
= ×
S
3
V
EQUATION2062-ANSI V1 EN-US
= ×
S
3
V
EQUATION2063-ANSI V1 EN-US
© 2017 - 2022 Hitachi Energy. All rights reserved
*
*
×
+
×
+
×
I
V
I
V
I
A
B
B
C
C
*
*
×
-
×
I
V
I
A
BC
C
*
×
I
PosSeq
PosSeq
*
*
×
-
(
I
I
)
A
B
*
*
×
-
(
I
I
)
B
C
*
*
×
-
(
I
I
)
C
A
*
×
I
A
A
*
×
I
B
B
*
×
I
C
C
1MRK 505 372-UUS Rev. K
*
Busbar protection REB670
Commissioning manual
(Equation 4)
(Equation 5)
(Equation 6)
(Equation 7)
(Equation 8)
(Equation 9)
(Equation 10)
(Equation 11)
(Equation 12)