INSTALLATION

The K-Factor scaler was designed with terminal connections with removable plugs for easy connection and removal from the
system after installation See
meter input and the pulse output to a totalizing device
Voltage Input
8.5...30V DC
Pulse Output

Enclosure Mounting (necessary for CSA certification)

If the circuit board assembly is supplied without an enclosure, it must be mounted within a certified Appleton one inch NPT
model GRL100-A or GRLB100-A conduit outlet box to maintain the CSA "Ordinary Locations" certification The label containing
the hookup information should be placed on the inside of the cover of the enclosure The label containing the CSA logo
should be placed on the bottom exterior of the enclosure

Power

The K-factor scaler requires 8 5...30V DC to operate The power connections are reverse polarity protected by a diode, but
must be connected properly for operation of the device Polarity is shown in

Turbine Meter

The turbine meter connections are non-polarized and located on a separate 2-position terminal Use shielded, twisted pair
wire for this connection
June 2021
Figure 2
for the I/O terminal connections The board connections include voltage input, turbine
P1
0
0
,
9 9 9 9 9 9 9 9
Figure 2: Input/Output terminal connections
SGN-UM-00281-EN-06
ON C &K S DA 0 5
S10
1 2 3 4 5
0
0
0
0
0
0
,
P2
P4
Figure 2
DIP Switches
(for selecting pulse width,
pulse state and pullup
resistor options)
Turbine Meter
Input
Factory Use Only
Installation
Page 7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Blancett b220-881Blancett b220-882Blancett b220-885

Table of Contents