SECTION 3 - START SEQUENCE

3.4.6 BMK4000 Air/Fuel Valve Position and Energy Input

TABLE 3-6a: BMK4000 Air/Fuel Valve Position – NATURAL GAS
AIR/FUEL VALVE POSITION
(% OPEN)
23% (Stop Level)
30%
40%
50%
60%
70%
80%
90%
100%
OMM-0137_E • GF-211 •
12/13/2019
ENERGY INPUT
(BTU/HR.)
228,180
456,900
822,800
1,205,000
1,684,000
2,388,000
3,107,000
3,582,000
4,000,000
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
5.7%
11.4%
20.6%
30.1%
42.1%
59.7%
77.7%%
89.6%
100%