SECTION 7 – BOILER SEQUENCING TECHNOLOGY
7.3.7 Option 7 Remote Setpoint: Modbus Header Temp Sensor & 4-
20ma Setpoint Drive
OPTION 7 Instructions: Remote Setpoint, Modbus Header Temp Sensor & 4-20ma Setpoint
Drive
NOTE:
Both Header Temp Sensor and 4-20ma Direct Drive must be wired. See the Edge
Controller Manual (OMM-0139, GF-213) for more information.
HEADER TEMP SENSOR WIRING – ANY BOILER
Step 1:
MODBUS
1. Connect the Modbus Transmitter terminal Pin B to the I/O board strip J3, terminal 13
(BST RS485+) and Pin A to terminal 15 (BST RS485–) on any of the Boiler units using
shielded pair 18 - 22 AWG cable.
2. Connect the shield to any Shield terminal, such as terminal 3 or 8 on strip J3.
3. Connect the Header Temp Sensor to pins 2 and 3 of the Modbus Transmitter units using
shielded pair 18 - 22 AWG cable.
3. Install a jumper wire between pins 1 and 2 of the Modbus Transmitter.
NOTES:
Polarity must be observed for the RS485 connections.
Ground the shield to any Shield terminal on the I/O board, such as terminal 3.
The Header Temp Sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant's supply water header.
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
HEADER TEMP SENSOR
Step 2: DIRECT WIRED 0-20mA OR 4-20mA WIRING – BST MANAGER
1. Connect the 4-20mA or 0-20mA terminals from the Direct Drive source to the I/O board
strip J3, terminal 6 (Remote Analog In +) and terminal 7 (Remote Analog In –) on the BST
Manager.
2. Connect the shield to any Shield terminal on the I/O board, such as terminal 3 or 8.
NOTES:
Shielded pair 18 - 22 AWG cable is recommended for this connection. Polarity must be
observed.
The ground for the shield is at the driver signal source.
OMM-0137_E • GF-211 •
12/13/2019
MODBUS TRANSMITTER
Continued on next page
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
3 Shield
13 BST RS485+
15 BST RS485–
I/O BOARD STRIP J3